ITEM | UNIT | SPECIFICATION | REMARKS | |
MODEL | | SIN2002C3 | | |
CAPACITY | VA/W | 25000/16250 | | |
AC INPUT | VOLTAGE | V | THREE PHASE, 4 WIRE 380 V | ± 15% |
FREQUENCY | Hz | 50 Hz ± 5% | | |
PROTECTION | | NO FUSE BREAKER | | |
DC INPUT | VOLTAGE | V | 192 | |
INTERNAL BATTERY | | 16 x 12V, 38 AH | SEALED LEAD ACID BATTERY | |
PROTECTION | | NO FUSE BREAKER | | |
CHG | TOPOLOGY | | SWITCHING REGULATION | |
FLOATING VOLTAGE | V | 217.6 | | |
INVERTER OUTPUT | WAFE FORM | | SINUSOIDA | |
DISTORTION | | <> | LOAD FROM 0 - 100% | |
TOPOLOGY | | PULSE WIDTH MODULATION (PWM) | | |
VOLTAGE | V | 220V ± 2% | | |
FREQUENCY | Hz | 50 Hz ± 1% | | |
EFFICIENCY | % | ± 85% | AT FULL LOAD | |
TRANSFER TIME WHEN AC INPUT LOSS | ms | 0 | ON-LINE / CONTINUOUS | |
STATIC TRANSFER SWITCH | ms | 2 ms FROM INVERTER TO BY-PASS, 0 ms BACK TO INVERTER | | |
BACK UP TIME | min | 10 | AT NOMINAL LOAD | |
BUZZER | UPS IN BY-PASS CONDITION | | INTERMITTENT SOUND WITH 30 SECONDS INTERVAL | WARNING THAT UPS IN BY-PASS CONDITION |
AC INPUT ABNORMAL | | INTERMITTENT SOUND WITH 4 SECONDS INTERVAL | AC INPUT LOSS OR LESS THEN 185 V | |
BATTERY LOW | | INTERMITTENT SOUND WITH 1 SECOND INTERVAL | | |
OPERATION TEMPERATURE | °C | 0 - 40 | | |
DIMENSION | mm | 870 x 595 x 1315 | D x W x H | |
WEIGHT | Kg | 490 | |